Safety Controller
GC series
Safety relay output unitGC-S1R
Specifications
Model |
GC-S1R |
|||
Input/output points |
Safety inputs |
- |
||
Safety outputs |
||||
Safety relay output |
1 (3a) |
|||
AUX outputs |
- |
|||
Test outputs |
||||
Safety input specifications |
Input device |
|||
Input type |
||||
ON level (voltage/current) |
||||
OFF level (voltage/current) |
||||
Short-circuit current |
||||
Protection circuit |
||||
Maximum cable length |
||||
Safety output specifications |
Output type |
|||
Maximum load current |
||||
Residual voltage (during ON) |
||||
Leakage current (during OFF) |
||||
Maximum capacitive load |
||||
Load wiring resistance |
||||
Protection circuit |
||||
Maximum cable length |
||||
Safety relay output specifications |
Output type |
Relay (3a) (Externally-protected outputs)*1 |
||
Rated load (resistance load) |
250 VAC 6A / 30 VDC 6A*2 |
|||
Rated load (inductive load) |
240 VAC 2A (AC-15) / 24 VDC 1A (DC-13) |
|||
Relay output mechanical life |
Resistance load (250 VAC 6A/30 VDC 6A): Min. 100,000 times |
|||
Maximum cable length |
Max. 100 m328.1' |
|||
B10d |
With rated load: 400,000 |
|||
Test output specifications |
Output type |
- |
||
Maximum load current |
||||
Protection circuit |
||||
Maximum cable length |
||||
AUX output specifications |
Output type |
|||
Maximum load current |
||||
Residual voltage (during ON) |
||||
Leakage current (during OFF) |
||||
Protection circuit |
||||
Maximum cable length |
||||
Applicable standards |
EMC |
EMS: IEC 61131-2/-6, EN61131-2/-6,EMI: IEC 61131-2, FCC Part15B Class A, ICES-003, Class A |
||
Safety |
IEC 61508, EN 61508 SIL3, IEC 62061, EN 62061 SIL CL3, ISO/EN 13849-1:2015 Cat. 4, PL e |
|||
Dimensions |
39.6×95×90 mm1.56"×3.74"×3.54"(W×D×H) |
|||
Power supply |
Power voltage |
- |
||
Power consumption |
Max. 80 mA |
|||
Environmental resistance |
Ambient temperature |
−10 to +55 °C14 to 131 °F(No freezing) |
||
Storage temperature |
-25 to +70 °C-13 to 158 °F(No freezing) |
|||
相对湿度 |
5 to 85% (No condensation) |
|||
Operating altitude |
Max. 2000 m6561.7' |
|||
Overvoltage category |
II (III for relay output part) |
|||
Pollution degree |
2 |
|||
Vibration resistance |
Frequency: 5 to 9 Hz, Half amplitude: 3.5 mm0.14" |
|||
Shock resistance |
Acceleration: 150 m/s2, Operating time: 11 ms, 3 times each in X, Y, Z directions |
|||
Material |
Polycarbonate |
|||
Weight |
Approx. 180 g |
|||
*1To comply with the requirements of IEC61131-2, connect 10 A fast blow fuse (IEC 60217) in series to each contact. |
||||